You are in:Home/Publications/Mitigation of Very Fast Transient Overvoltages at the More Sensitive Points in Gas-Insulated Substation

Dr. Abd Elrahman Said Abd Elrahman Mohamed Ghoniem :: Publications:

Title:
Mitigation of Very Fast Transient Overvoltages at the More Sensitive Points in Gas-Insulated Substation
Authors: A Said, Ebrahim A. Badran, and M. A. Abd-Allah
Year: 2012
Keywords: Not Available
Journal: Not Available
Volume: Not Available
Issue: Not Available
Pages: Not Available
Publisher: Not Available
Local/International: International
Paper Link: Not Available
Full paper Not Available
Supplementary materials Not Available
Abstract:

Switching operations in a gas insulated substations generate very fast transient over voltages (VFTO) which are dangerous for the transformer and the system insulation because of their short rise time. Under special circumstances the terminal over voltages can arise close to the transformer BIL. The suppression of VFTO is very important in GIS systems. Different techniques are applied to 245 kV GIS model. The simulation used ATP-EMTP package program to evaluate the VFTO at the sensitive points in GIS. The different results are compared to determine the effective mitigation method. The results show that the wave steepness and the amplitudes of VFTO can be reduced to about 1Pu with less oscillation frequency.