Worldwide many electrical equipment insulation
failures have been reported caused by switching operations, while
those equipments had previously passed all the standard tests and
complied with all quality requirements. The problem is mostly
associated with high-frequency overvoltages generated during
opening or closing of a switching device. The transients generated
during switching operations in a Gas Insulated Substation (GIS) are
associated with high frequency components in the order of few tens
of MHz.
The frequency spectrum of the VFTO generated in the 220/66 kV
Wadi-Hoff GIS is analyzed using Fast Fourier Transform technique.
The main frequency with high voltage amplitude due to the operation
of disconnector (DS5) is 5 to 10 MHz, with the highest amplitude at 9
MHz. The main frequency with high voltage amplitude due to the
operation of circuit breaker (CB5) is 1 to 25 MHz, with the highest
amplitude at 2 MHz.
Mitigating techniques damped the oscillating frequencies
effectively. The using of cable terminal reduced the frequency
oscillation effectively than that of OHTL terminal. The using of a
shunt capacitance results in vanishing the high frequency
components. Ferrite rings reduces the high frequency components
effectively especially in the range 2 to 7 MHz. The using of RC and
RL filters results in vanishing the high frequency components. |