Abstract
The widespread use of data centers, the dramatically increase of the data center power density and the need of improving cooling system efficiency to maintain reliable operation temperature and save cooling energy make the study of data center thermal management an urgent issue. In the current paper, three different configurations for thermal management solution of high power density data centers are investigated, compared and evaluated. A scaled physical model data center have been designed and constructed for the sake of the study using the theory of scale modeling of air flow experiments. The results showed that (i) by using aisle partition and aisle containment the rack inlet temperature can be reduced by 3–13% and 13%-15.5% for aisle partition and aisle containment configurations, respectively, (ii) the intake air temperature reduction increases with increasing power density, (iii) using aisle partitions and aisle containment with raised floor improves the data center cooling performance. |