You are in:Home/Publications/Particle-Initiated Corona and Breakdown Under dc/ac Mixed Voltages | |
Prof. mahmoud mohamed ahmed elbahy :: Publications: |
Title: | Particle-Initiated Corona and Breakdown Under dc/ac Mixed Voltages |
Authors: | M. A. Abd-Allah Sayed A. Ward |
Year: | 1999 |
Keywords: | Not Available |
Journal: | Not Available |
Volume: | Not Available |
Issue: | Not Available |
Pages: | Not Available |
Publisher: | Not Available |
Local/International: | International |
Paper Link: | Not Available |
Full paper | mahmoud mohamed ahmed elbahy_elbahy00804665.pdf |
Supplementary materials | Not Available |
Abstract: |
The influence of conducting particles on the corona onset voltage and the breakdown voltage in a uniform field gap under ac voltage superimposed with iiegativc dc biasing voltage is investigated. The effect of particle length, gap spacing and the dc biasing voltage 011 the corona onset and tlie breakdown voltages is also presented and discussed. The breakdown voltage of different gap spacing and dc biasing voltage is compared with calculated values. The comparison shows good agreement between experimental and calculated values. |