You are in:Home/Publications/Experimental Study on the Performance Enhancement of a Water Chiller

Dr. Mohamed Reda Aly Abd-Elhamid Salem :: Publications:

Title:
Experimental Study on the Performance Enhancement of a Water Chiller
Authors: M.M. Alkhaja; M.R. Salem; K.M. Elshazly; M.F. Abdrabbo
Year: 2018
Keywords: Helically coiled tube; Evaporator; Water chiller; Curvature; Torsion; Performance
Journal: Scientific Journal of October 6 University
Volume: Not Available
Issue: Not Available
Pages: Not Available
Publisher: October 6 University
Local/International: Local
Paper Link: Not Available
Full paper Mohamed Reda Aly Abd-Elhamid Salem_Manuscript - 1.pdf
Supplementary materials Mohamed Reda Aly Abd-Elhamid Salem_Manuscript - 1.pdf
Abstract:

This work experimentally investigates the effect of the geometrical parameters of a vertical helically coiled tube in tube (HCTIT) evaporator on the coefficient of performance (COP) of a vapour compression refrigeration system (VCRS) used as a water chiller. Five HCTIT evaporators through which R134a flows in the internal tube, are constructed and tested at different flow rates of the heating water in their annulus. They are geometrically divided into two groups; the first group is fabricated such that the internal tube curvature ratios (δ_(ev,i)) is varied from 0.0238 to 0.0334 while the other group represents another three-different coil torsions (λ) from 0.0522 to 0.0948. The results show that the COP of the VCRS is enhanced with decreasing δ_(ev,i), increasing λ, and increasing the condenser to evaporator pressures ratio. Finally, an experimental correlation is developed to predict the COP of the VCRS.

Google ScholarAcdemia.eduResearch GateLinkedinFacebookTwitterGoogle PlusYoutubeWordpressInstagramMendeleyZoteroEvernoteORCIDScopus