This paper investigates the dynamic behavior of wind farm based on DFIG wind turbines during three phase to
ground fault at wind farm terminals using different types of protection. Also, it schemes to improve fault ride through
(FRT) capability for keeping the machine connected to the grid during fault period without destroying the machine,
which is important to avoid a cascading effect due to lack of power and instability of the system. First, the system is
tested using only crowbar protection scheme with varying of its resistance, then using only DC-chopper with different
values of its resistance. Finally, the system is evaluated using both crowbar and DC-chopper. The transient behavior of
DC-link voltage, electromagnetic torque, reactive power, stator voltage and rotor speed during fault is evaluated and
compared with proposed types of protection schemes. |