You are in:Home/Publications/A NEW TECHNIQUE FOR TRANSIENT RECOVERY VOLTAGE SUPPRESSION ON GENERATOR CIRCUIT BREAKER FOR GENERATOR FED FAULTS | |
Prof. Abdel-Salam Hafez Abdel-Salam Hamza :: Publications: |
Title: | A NEW TECHNIQUE FOR TRANSIENT RECOVERY VOLTAGE SUPPRESSION ON
GENERATOR CIRCUIT BREAKER FOR GENERATOR FED FAULTS |
Authors: | Abdelsalam H. HAMZA Tamer ELYAN M. A. ABD-ALLA Ebrahim A. BADRAN |
Year: | 2013 |
Keywords: | Not Available |
Journal: | Not Available |
Volume: | Not Available |
Issue: | Not Available |
Pages: | Not Available |
Publisher: | Not Available |
Local/International: | International |
Paper Link: | Not Available |
Full paper | Abdel-Salam Hafez Abdel-Salam Hamza_A New Technique For Transient Recovery Voltage Suppression on Generator Circuit Breaker For Generator Fed Faults-1.pdf |
Supplementary materials | Not Available |
Abstract: |
In this paper, the generator circuit breaker (GenCB) is simulated using ATP- EMTP software package. Four main stages of the breaker’s operating processes are considered, namely; the closed contacts stage, the arc burning stage, the arc extinguishing stage and the opened contacts stage. Therefore, not only the dynamic conductance during current zero are considered but also the effects of arc voltage on the arcing times are included. The simulation is tested in a representative network and the results are compared with IEEE Generator Circuit Breaker standards. A new mitigation technique is introduced to reduce the transient recovery voltage and the rate of rise of re-striking voltage during switching period. The results show that the new technique reduces both the TRV and RRRV effectively with respect to previous ones. |